? Optimized energy efficiency of the system.
? Precision flow control with high resolution.
? Compact and lightweight.
? Energy saving design.
? Proven know-how and high reliability.
? Wide range for all common refrigerants.
? Bi-flow for heat pump applications.
?
Maximum working pressure 47 bar (667 psig)
Compatible refrigerants R134a, R404A, R407C, R410A, R22 and other refrigerant
Refrigerant oil All mineral oils and ester oils (to lubricate ETS 6 valve)
Ambient temperature -30°C to 70°C (-22 °F to 158° F)
Fluid Temperature -30°C to 70°C (-22 °F to 158° F)
Durability
Tested for 60 Million total pulses supplies to the valve during partially open
valve, which is comparable to 150,000 cycles if the valve is operated between
100 to 300 pulses open.
Tested for 30,000 full stroke cycles including 20 pulse overdrive at each closing.
Ambient humidity 95% RH or less
Modulation Permanent magnet type direct operating stepper motor
Excitation method 1-2 phase
Electrical connection JST XHP-6 and JST XHP-5
Excitation speed min. 30 pps (pulses per second) to max. 90 pps, recommended pps
Operating range
0 to 480 pulses, no holding power required (NOTE: do not apply more than
520 pulses)
Full motion transit time 16 sec @ 30 pps, 6 sec @ 80 pps
Installation position
Liquid line solenoid valve
With coil on the upper side and the valve/coil assembly within ±15?of the
vertical axis
If using a liquid line solenoid valve, it must be installed in such a way that it
does not create liquid hammering this ETS 6 valve
Max. coil winding temperature 115 °C (239 ° F)
基本原理:
The ETS 6 electronic expansion valves open and
close to regulate refrigerant flow by means of
a screw, whose rotating motion is transformed
into linear motion. This occurs by the rotation
of a magnet-needle valve assembly which
moves when electrical signals are applied to the
surrounding coil.
Within the coil structure, there are different
winding configurations, and the polarities are
changed by the electrical signals applied. By
application of the appropriate combination of
signals, in the form of pulses, the coil forces the
rotor of the valve to move in a stepwise fashion.
Application of multiple pulses will make the valve
mechanism to move through a series of steps
in the chosen direction, in order to set the valve
with the required opening degree.
丹佛斯ETS6-25-32,ETS6-40,034G5065系列電子膨脹閥的型號
ETS 6 - 10 1 2
90° 47
35 35
bi-flow
034G5005 034G5000
ETS 6 - 14 35 20 034G5015 034G5010
ETS 6 - 18 35 28 034G5026 034G5024
ETS 6 - 25 23 35 22 034G5035 034G5030
ETS 6 - 32 2 28 12* 034G5055 034G5050
ETS6 - 40 4 46 21 7 034G5065 034G5060