Product description:
I. overview
Alternating current (voltage) is a transmitter can be measured AC current (voltage) into the instrument according to the linear ratio of the output DC voltage or DC current, widely used in electric power, telecommunications, petroleum, coal, metallurgy, railway, municipal and other departments of the electrical device, automatic control and scheduling system. AC current and voltage transmitter have single -, three - way combined structure:
1, high accuracy (typical: 0.2% best 0.05%).
2, the entire range has a very high linearity.
3, a high degree of integration, simple structure, excellent temperature characteristics and long-term stability of the work, so that the transmitter from the regular calibration.
Two, product name and model
Name
Model
Auxiliary power
Single AC current transducer
LSD-I, LSE-I, YWF-I, YWL-I
YWD series optional: AC:220V 110V
DC:220V 110V 48V 24V
YWE, YWF, YWL series optional:
DC:24V, 15V, 12V
Three combined AC current transmitter
YWD-3I, LSE-3I, YWL-3I
Single AC voltage transmitter
LSD-U, YWE-U, YWF-U, YWL-U
Three combined AC voltage transmitter
YWD-3U, YWE-3U, YWL-3U
Three, the implementation of standards
GB/T13850-1998idtIEC688:1992
Four, the main technical indicators
A) accuracy level: level 0.2, level 0.5
B) input, output and auxiliary power parameters
Vn
input voltage
V0
0 ~ 70V
V1
0 ~ 120V
V2
0 ~ 250V
V3
0 ~ 300V
V4
0 ~ 450V
V5
0 ~ 500V
V6
Custom user
An
Input current
A1
0 ~ 1A
A2
0 ~ 5A
A3
0 ~ 10A
A4
0 ~ 30A
A5
0 ~ 50A
Note:
A4, A5, A6, A7, A8
Products suitable for class YWF structures only.
A6
0 ~ 75A
A7
0 ~ 100A
A8
0 ~ 150A
A9
User defined
Pn
Auxiliary power supply
P1
DC24V± 15%
P2
DC12V± 15%
P3
AC220V± 15%
P4
Custom user
On
Output
O1
0 ~ 5V
O2
1 ~ 5V
O3
0 ~ 2OmA
O4
4 ~ 20mA
O5
Custom user
C) input frequency: 50Hz± 5Hz
D) overload input: current: 2 times continuous for 30 second
Voltage: 2 times continuous
E) absorption power: voltage loop: 0 5VA/450V
Voltage loop: 0.2VA/100V
Current loop: 0.1 VA/5A
F) response time: ≤ 350ms
G) output load: current: when auxiliary power supply ≥ 24V, RL≤ 650Ω;
When the auxiliary power supply for 12V, 15V, RL≤ 300Ω;
Voltage: RL≥ 2kΩ
H) power frequency withstand voltage: input / output / enclosure: AC 2kV/min
I) insulation resistance: ≥ 20MΩ
J) impulse voltage: 5kV/1.2-50μ s (peak)
K) working environment: temperature: -10 to 50 degrees Celsius humidity: 10 ~ 90% (no condensation)
L) storage conditions: temperature: -40 to 70 degrees Celsius humidity: 10 ~ 95% (no condensation)
And, lt;, FONT size=2>m) dimensions:
YWD-I, YWD-U: 55 mm× 75 mm× 120mm3
YWD-3I, YWD-3U: 110 mm× 75 mm× 120mm
YWE-I, YWE-U: 42mm× 75 mm× 70mm
YWE-3I, YWE-3U: 110 mm× 75 mm× 70mm
YWF-I, YWF-3U: 104 mm× 31 mm× 77mm
YWL-I (3I), YWL-U (3U): 75 mm× 22.5mm× 100mm
Five, wiring diagram
1, YWD series single AC current (voltage) / three combined AC current (voltage) transmitter
2 YWE series single AC current (voltage) / three combined AC current (voltage) transmitter
3 YWF series single alternating current (voltage) transmitter
YWF-I YWF-U
4 YWL series single AC current (voltage) / three combined AC current (voltage) transmitter
Note: 1, YWF, YWL series AC current transmitter input line from the transmitter shell set through the perforation, regardless of polarity.
2, YWD, YWE series current transmitter allows only less than 10A of the current, more than 10A, can only choose YWF-I type products.
Six, product debugging
1, YWD, YWE single AC current, voltage transmitter: to find corresponding to the transmitter panel corresponding to the ZERO and CAL two debugging holes
Inside the two potentiometers are zero and full adjustment potentiometer, adjust with a small screwdriver slowly rotating to the required accuracy can be.
2, YWD, YWE three AC current, voltage combination transmitter: find corresponding to the transmitter panel corresponding to ZEROA, CALA,
ZEROB, CALB, and ZEROC, CALC six debugging holes, the potentiometer in the A, B, C three, respectively, the zero and full adjustment potential
When the utility model is adjusted, the utility model can slowly rotate to the required precision with a small screwdriver.
Seven, installation
YWD, YWE series uses two types of DIN rail and screw installation, rail width of 35mm. Screw size is M4× 12 and M3× 12. YDF, YWL using DIN rail installation, rail width of 35mm.
Eight, ordering information
When signing the contract, please specify in detail the required models, specifications, corresponding to the selected models in the following format will be code to fill in, with a special specification.
Example 1:YWF-I-A4-P1-O1
YWF-I active single AC current transmitter
Input: AC 0 ~ 30A
Auxiliary power supply: DC 24V± 15%
Output: DC 0 ~ 5V
Example 2:YWD-3U-V3-P3-O4
YWD-3U active three voltage combined transmitter
Input: AC 0 ~ 300V
Auxiliary power supply: AC 220V± 15%
Output: DC 4 ~ 20mA
Nine, matters needing attention
1, input, output, auxiliary power wiring must be correct, can not be misplaced.
2, the use of the environment should be no conductive dust and non corrosive metal and the destruction of insulating gases exist, altitude less than 2500 meters.
3, the factory has been adjusted zero and precision, please do not adjust.