I. overview
The transmitter is based on SCM, the latest algorithm to achieve the accurate measurement of AC circuit frequency. In the domestic similar products in the leading level.
Two, product name and model
Frequency transmitter: Type: YWD-F
Frequency transmitter: Type: YWE-F
Three, the implementation of standards
GB/T13850-1998idtIEC688:1992
Four, the main technical indicators
A) accuracy level: level 0.2;
B) input, output, auxiliary power supply and measuring range parameters:
Vn V1 100VV2 220VV3 270VV4 380VV5 input voltage Fn F1 custom frequency range 45 ~ 55HzF2 48 ~ 52HzF3 40 ~ 60HzF4 0 ~ 10kHzF5 custom Pn P1 auxiliary power supply DC 24V± 10%P2 DC12V± 10%P3 AC220V± 10%Pn custom note: YWD auxiliary power series: AC220, AC110 or On passive output specifications O1 0 ~ 5VO2 1 ~ 5VO3 0 ~ 20mAO4 4 ~ 20mAO5 0 ~ 10kHzOn user
C) power consumption: ≤ 1W (24V)
D) overload input: 2 times continuous
E) absorption power consumption: ≤ 0.22VA/220V
≤ 0.10VA/100V
F) response time: ≤ 400s
G) load capacity: current output: ≤ 750Ω (220V), voltage output: ≥ 2kΩ
H) power frequency withstand voltage: AC2kV/min× 1mA
I) insulation strength: ≥ 100MΩ
J) working environment: temperature: -10 to 50 degrees Celsius, humidity: 10 ~ 90% (no condensation)
K) storage conditions: temperature: -40 to 70 degrees Celsius, humidity: 10 ~ 95% (no condensation)
L) dimensions:
YWE-F: 42 mm× 75 mm× 70mm
YWD-F: 55 mm× 75 mm× 70mm
Five, installation mode
DIN guide rail and screw two installation methods, the width of the guide rail 35mm. Screw size is M3× 12.
Six, ordering information
The signing of the contract should be to indicate whether the total output, and specify the required models, specifications, the selected models, specifications will be in the following format code will be filled with special specifications with text.
Example 1:YWD-F-V1-P3-F1-O4
YWD-F frequency transmitter
Input: AC 100V± 30%
Auxiliary power supply: AC 220V
Range: 45 ~ 55Hz
Output specification: DC4 ~ 20mA
Example 2:YWE-F-V2-P2-F2-O1
YWE-F frequency transmitter
Input: AC 220V± 30%
Auxiliary power supply: DC 12V± 10%
Range: 48Hz ~ 52Hz
Output specification: DC 0 ~ 5V
Seven, matters needing attention
1, the line must be shielded wire, and the power cord, the input line and the output line must be separated.
2, the use of the environment should be no conductive dust and non corrosive metal and the destruction of insulating gases exist, altitude less than 2500 meters.
3, the factory has been adjusted zero and precision, please do not adjust.